Appendix A.1.  1. How Client Stores Data: 
The  HCS will be polled  by an  RDBC  Map Descriptor  and data  will  be stored in  the 
DA_Current Data Array in the following fashion if parameter HCSR_Data_Stages >1: 
•  New data is stored as current data. 
•  If data is changed, last current data is moved to 2
nd
 Stage, 2
nd
 Stage data is moved 
to 3
rd
 stage and 3
rd
 stage data is lost. 
Appendix A.1.1.  Data_Type is Ana_Input or not specified 
Data Array Offset  Description 
Current Data   
0 - 18  Data bits ( 0 - 1 ) 
19  Receipt ok ( 0 ), Disturbance ( 1 )
20  From Loop ( 0 ), On Loop ( 1 ) 
21  Loop Number (1,2,3,4) as integer
2
nd
 (Previous) Data   
24 – 42  Data bits ( 0 – 1 ) 
43  Receipt ok ( 0 ), Disturbance ( 1 )
44  From Loop ( 0 ), On Loop ( 1 ) 
45  Loop Number (1,2,3,4) as integer
3
rd
 (Prior to previous) Data
48 – 66  Data bits ( 0 – 1 ) 
67  Receipt ok ( 0 ), Disturbance ( 1 )
68  From Loop ( 0 ), On Loop ( 1 ) 
69  Loop Number (1,2,3,4) as integer
Appendix A.1.2.  Data_Type is Digi_Input 
Data Array Offset (Say 0)  Description 
Current Data   
0 - 18  Data bits ( 0 - 1 ) 
19  Receipt ok ( 0 ), Disturbance ( 1 ) 
20  From Loop ( 0 ), On Loop ( 1 ) 
21,22,23  3 bits for Loop Number 
Offsets 
21 22 23 
1 0 0 –Loop 1 
0 1 0 –Loop 2 
1 1 0 –Loop 3 
0 0 1 –Loop 4 
2
nd
 (Previous) Data   
24 – 42  Data bits ( 0 – 1 ) 
43  Receipt ok ( 0 ), Disturbance ( 1 ) 
44  From Loop ( 0 ), On Loop ( 1 ) 
45  Loop Number (1,2,3,4) in 3 bits as above
3
rd
 (Prior to previous) Data
48 – 66  Data bits ( 0 – 1 ) 
67  Receipt ok ( 0 ), Disturbance ( 1 ) 
68  From Loop ( 0 ), On Loop ( 1 ) 
69  Loop Number (1,2,3,4) in 3 bits as above