User Guide
FS-8704-16 Omron FINS Manual          Page 31 of 37 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
ELEMENT 
NUMBER 
CONTENTS  DESCRIPTION 
1 
1 
2 
3 
CPU Status
9
1= Stop 
2= Standby (waiting for signal from another 
Device) 
3= Run 
2 
1 
2 
3 
CPU Mode 
1= PROGRAM 
2= MONITOR 
3= RUN 
3 1/0 1: Memory Error 
4  1/0  1: I/O Bus Error 
5 1/0 1:Duplication Error 
6  1/0  1:Fatal Inner Board Error 
7 1/0 1:I/O Point overflow 
8  1/0  1:I/O Setting Error 
9 1/0 1:Program Error 
10  1/0  1:Cycle Time Over 
11 0  - 
12 1/0  1:FALS Error 
13-18 0  - 
19 1/0  1:FAL Error 
20  Unknown  Reserved for System 
21 1/0  1:Interrupt Task Error 
22  1/0  1:Basic I/O Unit Error 
23  Unknown  Reserved for System 
24  1/0  1:PLC Setup Error 
25  1/0  1:I/O Verification Error 
26  1/0  1:Inner Board Error 
27  1/0  1:CPU Bus Unit Error 
28  1/0  1:Special I/O Unit Error 
29  1/0  1:Sysmac Bus Error 
30 1/0  1:Battery Error 
31  1/0  1:CPU Bus Unit Setting Error 
32  1/0  1:Special I/O Unit-Setting Error 
33-34  Unknown  Reserved for System 
35-42 0  - 
9
PLC Value  Driver Value  Meaning 
0x00 1  Stop 
0x80 2  Standby 
0x01 3  Run 
Note: During testing it has been found that the PLC Value corresponds with this book value. Hence the Driver 
stores or sends any other value as it is. User has to do some experiment on it.