User Guide
FS-8704-16 Omron FINS Manual          Page 22 of 37 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
Appendix A.2.  PLC status to execute commands 
PLC Type 
Memory 
Type 
Command name
Run 
Mode 
Monitor 
Mode 
Program 
Mode 
Access 
right 
5
UM Read 
Protection
6
DIP UM 
Protection
7
MEMORY AREA 
READ 
OK OK  OK  OK  OK  OK 
I/O Memory 
MEMORY AREA 
WRITE 
OK OK  OK  OK  OK  OK 
RUN OK OK OK Disabled OK  OK Operating 
Mode 
Changes 
STOP OK OK OK Disabled OK  OK 
CLOCK READ  OK  OK  OK  OK  OK  OK Time Data 
Access 
CLOCK WRITE  OK  OK  OK  Disabled  OK  OK 
CPU UNIT 
STATUS READ 
OK OK  OK  OK  OK  OK 
CS1/CJ1 
Series 
Status 
Reading 
CYCLE TIME 
READ 
OK OK  Disabled OK  OK  OK 
5
 Access Right at Other Device: The Access right at other device column tells whether the CPU Unit can or cannot receive a command when another device has 
the access right to the CPU Unit.
6
 UM Read Protection: The UM read protection column tells whether the CPU Unit can or cannot receive the command when UM (user memory) is protected 
from a Peripheral Device.
7
 DIP Switch UM Protection: The DIP switch UM protection column tells whether the CPU Unit can or cannot receive a command when UM is write-protected 
by turning ON pin 1 of the DIP switch on the CPU Unit’s front panel.