User Guide
FS-8704-16 Omron FINS Manual          Page 21 of 37 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
Appendix A. Advanced Topics 
Appendix A.1.  Driver Map Descriptor Parameter’s Bounds 
Most Map Descriptors need to know the following 
The Data Type to 
be read or written: 
Specify Either 
a) Data Type or 
b) Memory Code. 
This is how the driver determines which memory area of the 
PLC must be processed. (For EM Banks you can only specify 
the Memory_Code.) 
The Command to 
be executed 
Specify either 
a) The command name or 
b) The MRC/SRC Pair. 
Memory 
Type 
Data_Type  Memory_Code  Command_Name  MRC  SRC  Address
MEMORY AREA 
READ 
1 1 0-6143 
CIO-WORD B0 
MEMORY AREA 
WRITE 
1 2 0-6143 
MEMORY AREA 
READ 
1 1 0-511 
WR-WORD B1 
MEMORY AREA 
WRITE 
1 2 0-511 
MEMORY AREA 
READ 
1 1 0-511 
HR-WORD B2 
MEMORY AREA 
WRITE 
1 2 0-511 
MEMORY AREA 
READ 
1 1 0-959 
AR-WORD B3 
MEMORY AREA 
WRITE 
1 2 448-959
MEMORY AREA 
READ 
1 1 0-32767
DM-WORD 82 
MEMORY AREA 
WRITE 
1 2 0-32767
MEMORY AREA 
READ 
1 1 0-32767
EM-WORD 
98 
Present Current 
EM Bank 
MEMORY AREA 
WRITE 
1 2 0-32767
MEMORY AREA 
READ 
1 1 0-32767
I/O 
Memory 
Not Available 
(Use only 
memory_code) 
A0-AC 
(Any other EM 
Bank) 
MEMORY AREA 
WRITE 
1 2 0-32767