1.012  Server Side Map Descriptors 
5.1.1. FieldServer Specific Map Descriptor Parameters 
Column Title  Function  Legal Values 
Map_Descriptor_Name 
Name of this Map 
Descriptor 
Up to 32 alphanumeric 
characters 
Data_Array_Name 
Name of Data Array 
where data is to be 
stored in the FieldServer 
One of the Data Array names 
from “Data Array” section 
above 
Data_Array_Offset 
Starting location in Data 
Array 
0 to maximum specified in 
“Data Array” section above 
Function 
Function of Server Map 
Descriptor 
Server 
5.1.2.  Driver Specific Map Descriptor Parameters 
Column Title  Function  Legal Values 
Node_Name 
Name of Node to fetch 
data from 
One of the node names 
specified in “Server Node 
Descriptor” above 
*Data_Type 
(see Note1 Appendix A.1) 
Data type 
CIO-WORD, WR-WORD, 
HR-WORD, AR-WORD, 
EM-WORD 
Length  Length of Map Descriptor 
1 to maximum specified in 
Data Array section above 
*Address 
Starting address of read 
block 
0,100, 32767 etc 
see section 6.1 for detail 
*Memory_Code 
(see Note1 Appendix A.1) 
Memory code for PLC 
memory type 
B0, B1, B2, B3, 82, 98 and 
A0 ---- AC 
*Command_Name 
(see Note2 Appendix A.1) 
Name of the command 
MEMORY AREA READ 
MEMORY AREA WRITE 
RUN-STOP 
CLOCK READ 
CLOCK WRITE 
CYCLE TIME READ 
CPU UNIT STATUS READ 
*MRC 
(see Note2 Appendix A.1) 
Main Request Code  1,4,6,7 
*SRC 
(see Note2 Appendix A.1) 
Sub Request Code  1,2,20 
*Unit_Number 
Unit number of CPU at 
PLC 