5.  Configuring the FieldServer as a FINS Server 
For a detailed discussion on FieldServer configuration, please refer to the FieldServer 
Configuration Manual. The information that follows describes how to expand upon the 
factory defaults provided in the configuration files included with the FieldServer (See 
“.csv” files on the driver CD). 
This section documents and describes the parameters necessary for configuring the 
FieldServer to communicate with a FINS Client. 
As a Server, the Driver responses to read requests and updates the FieldServer Data 
Arrays with write requests from the Client. 
The configuration file tells the FieldServer about its interfaces, and the routing of data 
required. In order to enable the FieldServer for FINS communications, the driver 
independent FieldServer buffers need to be declared in the “Data Arrays” section, the 
FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, 
and the data to be provided to the clients needs to be mapped in the “Server Side Map 
Descriptors” section. Details on how to do this can be found below. 
Note that in the tables, * indicates an optional parameter, with the bold legal value being 
the default. 
1.010  Server Side Connection Descriptors 
Section Title 
Adapter 
Column Title  Function  Legal Values 
Adapter  Adapter Name  N1, N2
4
Protocol  Specify protocol used  Fins, omn_fins or fins_udp 
Udp_port_number Specify UDP port number  0,9600 etc 
Example
// Server Side 
Connections 
Adapters 
Adapter,  Protocol,  Udp_port_number 
N1,  Fins,  9600 
4
 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for 
details of the ports available on specific hardware.