User Guide
FS-8704-16 Omron FINS Manual          Page 8 of 37 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
Example 
// Client Side 
Connections 
Adapters 
Adapter,  Protocol,  Udp_port_number 
N1,  Fins,  9600 
1.08  Client Side Node Descriptors 
Section Title 
Nodes 
Column Title  Function  Legal Values 
Node_Name  Provide name for node 
Up to 32 alphanumeric 
characters 
IP_Address  Provide IP Address of PLC  Eg. 192.168.1.105 
Node_ID 
Node number set at PLC 
The node number should 
correspond to the last byte of 
the IP address. Eg. 105 
corresponds to the example IP 
address above. 
1-126 
Protocol Specify protocol used  Fins, omn_fins or fins_udp 
Adapter 
Specify which port the device is 
connected to the FieldServer 
N1, N2
3
*Net_Number 
Provide the network number of 
PLC 
1-255 
Example
// Client Side Nodes 
Nodes           
Node_Name,  IP_Address,  Node_ID,  Protocol,  Adapter,  Net_Number 
PLC 1,  192.168.1.5,  1,  Fins,  N1,  1 
3
 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for 