User Guide
FS-8704-11 Telnet Driver Manual  Page 4 of 6 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
4.  Using the Serial Port Capture 
4.1.  Manual Serial Port Capture 
•  Once the FieldServer is up and running, connect to it using its IP address. 
•  Type port <Enter> 
•  When prompted, enter the name of the port to be captured (e.g. P8 <Enter>). The 
driver will check if the desired port has been initialized by a “port” statement in the 
configuration file. If the port has been initialized and is available, the driver will wait 
for any current polls to finish, and will then print “Connected” to indicate that the port 
is now under the control of the Telnet client. If a device is connected to the captured 
serial port, you can now communicate with it as if you had a direct serial connection. 
•  To disconnect the port from the Telnet session, press Ctrl-C. This will also work 
while the driver is still waiting for an active poll to complete. 
•  To terminate the Telnet session, close the Telnet client. 
Notes: 
1.  If a port has been manually captured in one Telnet session, it will not be available to 
any other Telnet sessions. Other sessions attempting to capture the port will be 
returned to the command prompt with an error message. To release a port, the 
connected Telnet session must be disconnected. 
2.  Capturing a port makes the port unavailable to any protocol driver on the FieldServer 
that might have been communicating with the device. Refer to the comments on 
session_timeout above on how to prevent an indefinite lockout if a Telnet session 
with a port capture is forgotten on. 
3.  A Serial connection needs to be specified before defining the Telnet connection 
(which has autoconnect_port) or else the FieldServer will give system error. 
Example 
Not Correct: 
Connections 
Adapter,  Protocol,  Autoconnect_port 
N1,  TLN,  P1 
Correct: 
Connections 
Adapter,  Baud,  Timeout,  Protocol 
P1,  9600,  10s,  - 
Connections 
Adapter,  Protocol,  Autoconnect_port 
N1,  TLN,  P1 