FS-8700-97_Lutron_Machine Manual    Page 9 of 11 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
4.3.  Client Side Node Descriptors 
Section Title 
Nodes 
Column Title  Function  Legal Values 
Node_Name  Provide name for node  Up to 32 alphanumeric characters 
Node_ID 
The eLumen processor address. 
Only decimal values are allowed: 
e.g. 11 hex must be entered as 
17. 
0-255 
Protocol  Specify protocol used  eLumen 
Connection 
Specify which port the device is 
connected to the FieldServer 
P1-P8, R1-R2
1
Node_type 
Specifies the eLumen command 
and data format 
Hex, decimal 
Example
// Client Side Nodes 
Nodes         
Node_Name,  Node_ID,  Protocol,  Port,  Node_Type 
LUT_GRF6_0,  17,  eLumen,  P1,  Hex 
4.4.  Client Side Map Descriptors 
4.4.1. FieldServer Related Map Descriptor Parameters 
Column Title  Function  Legal Values 
Map_Descriptor_Name 
Name of this Map 
Descriptor 
Up to 32 alphanumeric 
characters 
Data_Array_Name 
Name of Data Array 
where data is to be 
stored in the 
FieldServer 
One of the Data Array 
names from “Data Array” 
section above 
Data_Array_Offset 
Starting location in Data 
Array 
0 to maximum specified in 
“Data Array” section above 
Function 
Function of Client Map 
Descriptor 
ARCO, AWT, RDBC, 
Passive_Client 
4.4.2.  Driver Related Map Descriptor Parameters 
Column Title  Function  Legal Values 
Node_Name  Name of Node to fetch data from 
One of the node names 
specified in “Client Node 
Descriptor” above 
Grafik_Command 
Specifies the command that will be 
sent to the eLumen. 
Area Machine:
run_script_AB 
area_sts_offscene 
sel_scene_in_area 
run_script_multi 