User Guide
FS-8700-97_Lutron_Machine Manual    Page 8 of 11 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
4.2.  Client Side Connection Descriptions 
Section Title 
Connections 
Column Title  Function  Legal Values 
Port 
Specify which port the device 
is connected to the 
FieldServer 
P1-P8, R1-R2
1
Protocol  Specify protocol used  eLumen 
Baud*  Specify baud rate  9600 
Parity* Specify parity  None 
Data_Bits*  Specify data bits 
8 
Stop_Bits*  Specify stop bits 
1 
Handshaking* 
Specify hardware 
handshaking 
None 
Poll _Delay*  Time between internal polls  0-32000 seconds, 1 second 
Example
// Client Side Connections 
Connections 
Port,  Protocol,  Baud,  Parity,  Handshaking,  Poll_Delay 
P1,  eLumen,  9600,  None,  None,  0.100s 
1
  Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction 
manual for details of the ports available on specific hardware.