User Guide
FS-8700-97_Lutron_Machine Manual    Page 7 of 11 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
4.  Configuring the FieldServer as a Lutron Machine Client 
For a detailed discussion on FieldServer configuration, please refer to the FieldServer 
instruction manual. The information that follows describes how to expand upon the factory 
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files 
provided with the FieldServer). 
This section documents and describes the parameters necessary for configuring the FieldServer 
to communicate with a Lutron eLumen panel.  
4.1. Data Arrays/Descriptors 
The configuration file tells the FieldServer about its interfaces, and the routing of data 
required. In order to enable the FieldServer for Lutron Machine communications, the driver 
independent FieldServer buffers need to be declared in the “Data Arrays” section, the 
destination device addresses need to be declared in the “Client Side Nodes” section, and 
the data required from the Servers needs to be mapped in the “Client Side Map Descriptors” 
section. Details on how to do this can be found below. 
Note that in the tables, * indicates an optional parameter, with the bold legal value being the 
default. 
Section Title 
Data_Arrays 
Column Title  Function  Legal Values 
Data_Array_Name  Provide name for Data Array 
Up to 15 alphanumeric 
characters 
Data_Array_Format 
Provide data format. Each Data 
Array can only take on one format. 
Float, Bit, UInt16, SInt16, 
Packed_Bit, Byte, 
Packed_Byte, 
Swapped_Byte 
Data_Array_Length 
Number of Data Objects. Must be 
larger than the data storage area 
required by the Map Descriptors for 
the data being placed in this array. 
1-10,000 
Example
// Data Arrays     
Data_Arrays     
Data_Array_Name,  Data_Format,  Data_Array_Length 
Binary_Output,  Bit,  512 
Binary_Input,  Bit,  512 
Analog_Output,  Uint16,  512 
Analog_Input,  Uint16,  512 