4.4.14.  Map Descriptor Example 11 - Analog Value (Zone and Area Machine) 
A read from the Analog Value Data Array which is shared by a BACNet IP Map Descriptor will return the current value of a system 
variable in the Lutron eLumen panel. The variable values range from 0 to 255. The Lutron Machine Map Descriptors are regularly 
updated with system variable values from the active Binary Value Map Descriptors. A write to the Analog Value Data Array will set 
the system variable to the written value. 
BACNet IP Map Descriptor
// Client Side Map Descriptors 
Map_Descriptors                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Data_Type,  Object_ID,  Length,  Relinquish_Default 
SMD00_AV,  Analog_Value,  0,  Server,  Virtual_BCU_11,  AV,  1,  512,  0 
Lutron Machine Map Descriptor
// Client Side Map Descriptors 
Map_Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Grafik_Command,  Sys_Var,  Length 
Zone_vara_0,  Analog_Value,  0,  Passive_Client,  LUT_GRF6_0,  sys_var_val,  0,  512 
The Passive_Client function is used to prevent double-polling the Lutron eLumen panel for system variables. The Analog Value Map 
Descriptors should be set up identical to the Binary Value Map Descriptors in terms of the Sys_Var and Length fields to ensure 
system variable values will be stored correctly. 