4.4.12.  Map Descriptor Example 9 - Multistate Output (Zone and Area Machine) 
A write to the Multistate Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of multiple scripts. The 
multiple scripts are specified in the Data Array defined under “DA_Lut_List”. The value written into the Multistate Output Data Array 
is used as the offset into the Data Array defined under “DA_Lut_List” to retrieve a script number from the Data Array. Script numbers 
range from 0 to 65535. 
BACNet IP Map Descriptor
// Client Side Map Descriptors 
Map_Descriptors                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Data_Type,  Object_ID,  Length,  Relinquish_Default, 
SMD00_MO,  MultiSt_Output,  0,  Server,  Virtual_BCU_11,  MO,  1,  512,  0, 
Lutron Machine Map Descriptor 
// Client Side Map Descriptors 
Map_Descriptors                   
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Grafik_Command,  DA_Lut_List,  DA_Lut_List_Offset,  Length,  Multi_Scripts_Length 
Run_scriptms_0,  MultiSt_Output,  0,  AWT,  LUT_GRF6_0,  run_script_multi,  Scr_lst_MSO_0,  0,  1,  10 
The Multi_Scripts_Length field is used to indicate the maximum size of the Data Array specified under Data_Array_Name. One Map 
Descriptor per object must be defined with a Multi_Scripts_Length value of one or greater. 