4.4.11.  Map Descriptor Example 8 - Analog Input (Zone Machine) 
A read from the Analog Input Data Array which is shared by a BACNet IP Map Descriptor will return the intensity to which a given 
zone is set on the Lutron eLumen panel. The Lutron Machine Map Descriptor regularly polls the Lutron eLumen panel to retrieve the 
zone intensities. The intensity value returned is scaled to a percentage value (0 to 100%). Zone numbers range from 0 to 511. 
BACNet IP Map Descriptor
// Client Side Map Descriptors 
Map_Descriptors                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Data_Type,  Object_ID,  Length,  Relinquish_Default 
SMD00_AI,  Analog_Input,  0,  Server,  Virtual_BCU_11,  AI,  1,  512,  0 
Lutron Machine Map Descriptor
// Client Side Map Descriptors 
Map_Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Grafik_Command,  zone,  Length 
Zone_inta_0,  Analog_Input,  0,  ARCO,  LUT_GRF6_0,  zone_intensity,  0,  512 
The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of zones to poll. The 
start zone number is specified under the “zone” Map Descriptor field. More than one ARCO Map Descriptors may be used to poll two 
series of zone numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 fullfil the same function as RDBC 
Map Descriptors with the same length. 