Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
4.4.9.  Map Descriptor Example 6 - Analog Output 2 (Zone and Area Machine) 
A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of multiple scripts on the 
Lutron eLumen panel. The value written into the Analog Output Data Array is used as an offset into the Data Array defined under 
“DA_Lut_List” to retrieve a script number. Script numbers range from 0 to 65535. 
BACNet IP Map Descriptor
// Client Side Map Descriptors 
Map_Descriptors                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Data_Type,  Object_ID,  Length,  Relinquish_Default 
SMD512_AO,  Analog_Output,  512,  Server,  Virtual_BCU_11,  AO,  513,  512,  0 
Lutron Machine Map Descriptor
// Client Side Map Descriptors 
Map_Descriptors                   
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Grafik_Command,  DA_Lut_List,  DA_Lut_List_Offset,  Length,  Multi_Scripts_Length 
Run_script_512,  Analog_Output,  512,  AWT,  LUT_GRF6_0,  run_script_multi,  Scr_lst_AO2_512,  0,  1,  10 
The Multi_Scripts_Length field is used to indicate the maximum size of the Data Array specified under Data_Array_Name. One Map 
Descriptor per object must be defined with a Multi_Scripts_Length value of 1 or greater. 