4.4.7.  Map Descriptor Example 4 - Analog Output 1 (Area Machine) 
A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command an area to a preset scene on 
the Lutron eLumen panel. Scenes range from 0 to 65535 and area numbers range from 0 to 511 
BACNet IP Map Descriptor
// Client Side Map Descriptors 
Map_Descriptors                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Data_Type,  Object_ID,  Length,  Relinquish_Default 
SMD000_AO,  Analog_Output,  0,  Server,  Virtual_BCU_11,  AO,  1,  512,  0 
Lutron Machine Map Descriptor
// Client Side Map Descriptors 
Map_Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Grafik_Command,  area,  Length 
Sel_scene_0,  Analog_Output,  0,  AWT,  LUT_GRF6_0,  sel_scene_in_area,  0,  512 
The area field must be used to indicate the start area number that will be associated with the first element of the Data Array specified 
under Data_Array_Name. Area numbers increase with the Length field in association with increasing offset into the Data Array. 