4.4.5.  Map Descriptor Example 2 - Binary Input (Zone Machine) 
A read from the Binary Input Data Array which is shared by a BACNet IP Map Descriptor will return the relay state for the given zone. 
The Lutron Machine Map Descriptor regularly polls the eLumen panel to retrieve the value of zone intensity. The value of each 
BACNet object presenting Binary Output is inactive if the intensity is zero and active if the intensity is non-zero. Zone numbers range 
from 0 to 511 
BACNet IP Map Descriptor
// Client Side Map Descriptors 
Map_Descriptors                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Data_Type,  Object_ID,  Length,  Relinquish_Default 
SMD00_BI,  Binary_Input,  0,  Server,  Virtual_BCU_11,  BI,  1,  512,  0 
Lutron Machine Map Descriptor
// Client Side Map Descriptors 
Map_Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name,  Grafik_Command,  Zone,  Length 
Zone_int_0,  Binary_Input,  0,  ARCO,  LUT_GRF6_0,  zone_intensity,  0,  512 
The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of zones to poll. The 
start zone number is specified under the “Zone” Map Descriptor field. More than one ARCO Map Descriptor may be used to poll two 
series of zone numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 perform the same function as 
RDBC Map Descriptors with the same length. 