4.4.86.  Map Descriptor Example 82 - edit set events = event_list 
// Client Side Mao Descriptors 
Map Descriptor 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Cmd,  Par_Data_Array_Name,  Par_Data_Array_Offset,  Length 
Ed_Set_Events,  Par_Val_Trigger,  3,  awt,  SYSPLUS_01,  Ed_Set_Events,  Ed_Set_Events,  0,  10 
This command is used by first writing the parameter data event_list and then triggering the command by writing the number of events 
to Data_Array_Name at Data_Array_Offset. 
Note:
 Only consecutive events can be set ( eg. to set event9, all 10 events must be set and 10 written to Data_Array_Name ). 
Parameter data setup: (Use a value of 1 for “on” or a value of 0 for “off” per event) 
Offset from par_data_array_offset  Description 
0 
Event0 
.. 
.. 
9 
Event9 
4.4.87.  Map Descriptor Example 83 - edit set auxs = aux_list 
// Client Side Mao Descriptors 
Map Descriptor 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Cmd,  Par_Data_Array_Name,  Par_Data_Array_Offset,  Length 
Ed_Set_Auxs,  Par_Val_Trigger,  4,  awt,  SYSPLUS_01,  Ed_Set_Auxs,  Ed_Set_Auxs,  0,  10 
This command is used by first writing the parameter data aux_list and then triggering the command by writing the number of auxs to 
Data_Array_Name at Data_Array_Offset. Note: Only consecutive auxs can be set ( eg. to set aux1, all auxs from 0 to 1 must be set 
and 2 written to Data_Array_Name ). 
Parameter data setup: (Use a value of 1 for “on” or a value of 0 for “off” per aux) 
Offset from par_data_array_offset  Description 
0 
Aux0 
.. 
.. 
9 
Aux9 