User Guide
FS-8700-88 Envirotronics SystemsPlus            Page 34 of 49 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com 
4.4.84.  Map Descriptor Example 80 - edit set gsoak channel = value  
// Client Side Mao Descriptors 
Map Descriptor                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Cmd,  Par_Data_Array_Name,  Par_Data_Array_Offset,  Length 
Ed_Set_Gsoak,  Par_Val_Trigger,  1,  awt,  SYSPLUS_01,  Ed_Set_Gsoak,  Ed_Set_Gsoak,  0,  1 
This command is used by first writing the parameter data value and then triggering the command by writing channel to 
Data_Array_Name at Data_Array_Offset. 
Parameter data setup: 
Offset from par_data_array_offset  Description 
0 
Value 
4.4.85.  Map Descriptor Example 81 - edit set gsoak enabled channel = Boolean 
// Client Side Mao Descriptors 
Map Descriptor 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Cmd,  Par_Data_Array_Name,  Par_Data_Array_Offset,  Length 
Ed_Set_Gs_Ena,  Par_Val_Trigger,  2,  awt,  SYSPLUS_01,  Ed_Set_Gsoak_Ena,  Ed_Set_Gs_Ena,  0,  1 
This command is used by first writing the parameter data Boolean and then triggering the command by writing channel to 
Data_Array_Name at Data_Array_Offset. 
Parameter data setup: 
Offset from par_data_array_offset  Description 
0  Boolean 