User Guide
FS-8700-88 Envirotronics SystemsPlus            Page 33 of 49 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com 
4.4.82.  Map Descriptor Example 79 - set time = hour:minute:second  
// Client Side Mao Descriptors 
Map Descriptor                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Cmd,  Par_Data_Array_Name,  Par_Data_Array_Offset,  Length 
Set_Time,  Par_Bit_Triggers,  4,  awt,  SYSPLUS_01,  Set_Time,  Set_Time,  0,  1 
This command is used by first writing the parameter data and then triggering the command by writing any value to Data_Array_Name 
at Data_Array_Offset. 
Parameter data setup: 
Offset from par_data_array_offset  Description 
0 
Hour 
1 
Minute 
2 
Second 
4.4.83.  Map Descriptor Example 80 - edit set setpoint channel = value  
// Client Side Mao Descriptors 
Map Descriptor                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Cmd,  Par_Data_Array_Name,  Par_Data_Array_Offset,  Length 
Ed_Set_Setpoint,  Par_Val_Trigger,  0,  awt,  SYSPLUS_01,  Ed_Set_Setpoint,  Ed_Set_Setpoint,  0,  1 
This command is used by first writing the parameter data value and then triggering the command by writing channel to 
Data_Array_Name at Data_Array_Offset. 
Parameter data setup: 
Offset from par_data_array_offset  Description 
0 
Value 