User Guide
FS-8700-88 Envirotronics SystemsPlus            Page 23 of 49 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com 
4.4.47.  Map Descriptor Example 44 - use keypad = Boolean 
// Client Side Mao Descriptors 
Map Descriptor             
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Cmd,  Length 
Use_Keypad,  Use_Keypad,  0,  wrbx,  SYSPLUS_01,  Use_Keypad,  1 
A Boolean value of 1 for “true” or 0 for “false” must be written to Data_Array_Name at Data_Array_Offset to trigger this command. 
4.4.48.  Map Descriptor Example 45 - edit program program_num 
// Client Side Mao Descriptors 
Map Descriptor             
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Cmd,  Length 
Ed_Program,  Ed_Program,  0,  wrbx,  SYSPLUS_01,  Ed_Program,  1 
A program_num  value must be written to Data_Array_Name at Data_Array_Offset to trigger this command. 
4.4.49.  Map Descriptor Example 46 - edit step step_num 
// Client Side Mao Descriptors 
Map Descriptor             
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Cmd,  Length 
Ed_Step,  Ed_Step,  0,  wrbx,  SYSPLUS_01,  Ed_Step,  1 
A step_num  value must be written to Data_Array_Name at Data_Array_Offset to trigger this command. 
4.4.50.  Map Descriptor Example 47 - edit analog channel 
// Client Side Mao Descriptors 
Map Descriptor             
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Cmd,  Length 
Ed_Analog,  Ed_Analog,  0,  wrbx,  SYSPLUS_01,  Ed_Analog,  1 
A channel  value must be written to Data_Array_Name at Data_Array_Offset to trigger this command. 