User Guide
FS-8700-88 Envirotronics SystemsPlus            Page 19 of 49 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com 
4.4.32.  Map Descriptor Example 29 - read auxs 
// Client Side Map Descriptors 
Map Descriptor               
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
All_Aux_States,  0s,  All_Aux_States,  0,  rdbc,  SYSPLUS_01,  All_Auxs,  10 
The retrieved aux states will be stored as follows in Data_Array_Name: (A value of 1 will be stored for “on” or 0 for “off”) 
Offset from Data_Array_Offset  Description 
0  Aux_0 state 
1  Aux_1 state 
2  Aux_2 state 
..  .. 
9  Aux_9 state 
4.4.33.  Map Descriptor Example 30 - read alarm status alarm 
// Client Side Map Descriptors 
Map Descriptor                 
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Data_Type,  SysPlus_Alarm_Name,  Length 
Alarm_Sts_00,  0s,  Alarm_Statuses,  0,  rdbc,  SYSPLUS_01,  Alarm,  volt,  1 
alarm is specified by the name under SysPlus_Alarm_Name. The status of the alarm will be stored as 1 for “OK” or 0 for “FAIL” in 
Data_Array_Name at Data_Array_Offset. 
4.4.34.  Map Descriptor Example 31 - emergency stop 
// Client Side Map Descriptors 
Map Descriptors             
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Cmd,  Length 
Emergency_Stop,  ProgSysControl,  0,  wrbx,  SYSPLUS_01,  Emergency_Stop,  1 
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset. 