4.4.29.  Map Descriptor Example 26 - set audible alarm = Boolean 
// Client Side Map Descriptors 
Map Descriptor             
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Audible_Alarm,  Audible_Alarm_0,  0,  wrbx,  SYSPLUS_01,  Audible_Alarm,  1 
A Boolean value of 1 for “on” or 0 for “off” must be written to Data_Array_Name at Data_Array_Offset to trigger this command. 
4.4.30.  Map descriptor Example 27 - read software version 
// Cleint Side Map Descriptors 
Map Descriptor               
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Sw_Version,  0s,  Sw_Version,  0,  rdbc,  SYSPLUS_01,  Sw_Version,  1 
4.4.31.  Map Descriptor Example 28 - read events 
// Client Side Map Descriptors 
Map Descriptor               
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
All_Event_States,  0s,  All_Event_States,  0,  rdbc,  SYSPLUS_01,  All_Events,  10 
The retrieved event states will be stored as follows in Data_Array_Name: 
( A value of 1 will be stored for “on” or 0 for “off” ) 
Offset from Data_Array_Offset  Description 
0  Event_0 state 
1  Event_1 state 
2  Event_2 state 
..  .. 
9  Event_9 state 