4.4.26.  Map Descriptor Example 23 - read start time 
// Client Side Map Descriptors 
Map Descriptor               
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Start_Time,  0s,  Start_Time,  0,  rdbc,  SYSPLUS_01,  Start_Time,  4 
The retrieved start time will be stored as follows in Data_Array_Name: 
Offset from Data_Array_Offset  Description 
0  Month 
1  Day 
2  Hour 
3  Minute 
4.4.27.  Map Descriptor Example 24 - read stop time 
// Client Side Map Descriptor 
Map Descriptor               
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Stop_Time,  0s,  Stop_Time,  0,  rdbc,  SYSPLUS_01,  Stop_Time,  4 
The retrieved stop time will be stored as follows in Data_Array_Name: 
Offset from Data_Array_Offset  Description 
0 
Month 
1  Day 
2  Hour 
3  Minute 
4.4.28.  Map Descriptor Example 25 - read audible alarm 
// Client Side Map Descriptors 
Map Descriptor               
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Audible_Alarm,  0s,  Audible_Alarm,  0,  rdbc,  SYSPLUS_01,  Audible_Alarm,  1 
The status of the audible alarm will be stored as 1 for “on” or 0 for “off” in Data_Array_Name at Data_Array_Offset. 