User Guide
FS-8700-88 Envirotronics SystemsPlus            Page 16 of 49 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com 
4.4.23.  Map Descriptor Example 20 - set start time enabled = Boolean 
// Client Side Map Descriptors 
Map Descriptor             
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Start_Time_Ena,  Start_Time_Ena_0,  0,  wrbx,  SYSPLUS_01,  Start_Time_Ena,  1 
A Boolean value of 1 for “Enabled” or 0 for “Disabled” must be written to Data_Array_Name at Data_Array_Offset to  trigger this 
command. 
4.4.24.  Map Descriptor Example 21 - read stop time enabled 
// Client Side Map Descriptors 
Map Descriptor               
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Stop_Time_Ena,  0s,  Stop_Time_Ena,  0,  rdbc,  SYSPLUS_01,  Stop_Time_Ena,  1 
The stop time enabled status will be stored as 1 for “Enabled” or 0 for “Disabled” in Data_Array_Name at Data_Array_Offset. 
4.4.25.  Map Descriptor Example 22 - set stop time enabled = Boolean 
// Client Side Map Descriptors 
Map Descriptor             
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Stop_Time_Ena,  Stop_Time_Ena_0,  0,  wrbx,  SYSPLUS_01,  Stop_Time_Ena,  1 
A Boolean value of 1 for “Enabled” or 0 for “Disabled” must be written to Data_Array_Name at Data_Array_Offset to  trigger this 
command. 