User Guide
FS-8700-88 Envirotronics SystemsPlus            Page 15 of 49 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com 
4.4.19.  Map Descriptor Example 16 - read remaining step time 
// Client Side Map Descriptors 
Map Descriptor               
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Rm_Stp_Tm,  0s,  Rem_Steptime,  0,  rdbc,  SYSPLUS_01,  Rem_Step_Tim,  3 
The retrieved remaining step time will be stored as follows in Data_Array_Name: 
Offset from Data_Array_Offset  Description 
0  Hour 
1  Minute 
2  Second 
4.4.20.  Map Descriptor Example 17 -read start step 
// Client Side Map Descriptors 
Map Descriptor               
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Start_Step,  0s,  Start_Step,  0,  rdbc,  SYSPLUS_01,  Start_Step,  1 
4.4.21.  Map Descriptor Example 18 - set start step = step_num 
// Client Side Map Descriptors 
Map Descriptor             
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Start_Step,  Start_Step_0,  0,  wrbx,  SYSPLUS_01,  Start_Step,  1 
The step_num must be written into Data_Array_Name at Data_Array_Offset to trigger this command. 
4.4.22.  Map Descriptor Example 19 - read start time enabled 
// Client Side Map Descriptors 
Map Descriptor               
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  SysPlus_Data_Type,  Length 
Start_Time_Ena,  0s,  Start_Time_Ena,  0,  rdbc,  SYSPLUS_01,  Start_Time_Ena,  1 
The start time enabled status will be stored as 1 for “Enabled” or 0 for “Disabled” in Data_Array_Name at Data_Array_Offset. 