4.4.8.  Map Descriptor Example 5 - read setpoint channel 
// Client Side Map Descriptors 
Map Descriptors                 
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Data_Type,  Address,  Length 
Setpoints_00,  0s,  Setpoints,  0,  rdbc,  SYSPLUS_01,  Setpoint,  0,  1 
The channel is specified by the “Address” field. 
4.4.9.  Map Descriptor Example 6 - set setpoint channel = value 
// Client Side Map Descriptors 
Map Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Data_Type,  Address,  Length 
Setpoints_00,  Setpoints_0,  0,  awt,  SYSPLUS_01,  Setpoint,  0,  1 
The  channel  is  specified  by  the  “Address”  field.    value  is  retrieved  from  the  value  written  into  Data_Array_Name  at 
Data_Array_Offset. 
4.4.10.  Map Descriptor Example 7 - read pv channel 
// Client Side Map Descriptors 
Map Descriptors                 
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Data_Type,  Address,  Length 
Pvs_00,  0s,  Pvs,  0,  rdbc,  SYSPLUS_01,  Pv,  0,  1 
The channel is specified by the “Address” field. 
4.4.11.  Map Descriptor Example 8 - read deviation channel 
// Client Side Map Descriptors 
Map Descriptors                 
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Data_Type,  Address,  Length 
Deviation_00,  0s,  Deviations,  0,  rdbc,  SYSPLUS_01,  Deviation,  0,  1 