User Guide
FS-8700-88 Envirotronics SystemsPlus            Page 11 of 49 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com 
4.4.4.  Map Descriptor Example 1 - read event event_num 
// Client Side Map Descriptors 
Map Descriptors                 
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Data_Type,  Address,  Length 
Event_States_00,  0s,  Event_States,  0,  rdbc,  SYSPLUS_01,  Event,  0,  1 
The event_num is specified by the “Address” field. The state of the event will be stored as 1 for “ON” or 0 for “OFF”. 
4.4.5.  Map Descriptor Example 2 - set event event_num = Boolean 
// Client Side Map Descriptors 
Map Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Data_Type,  Address,  Length 
Event_States_00,  Event_States_0,  0,  awt,  SYSPLUS_01,  Event,  0,  1 
The event_num is  specified  by the “Address”  field.  The Boolean state  of the event is retrieved from the value written into 
Data_Array_Name at Data_Array_Offset. Use a value of 1 for “ON” and a value of 0 for “OFF”. 
4.4.6.  Map Descriptor Example 3 - read aux. aux_num 
// Client Side Map Descriptors 
Map Descriptor                 
Map_Descriptor_Name,  Scan_Interval,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Data_Type,  Address,  Length 
Aux_States_00,  0s,  Aux_States,  0,  rdbc,  SYSPLUS_01,  Aux,  0,  1 
The aux_num is specified by the “Address” field. The state of the aux will be stored as 1 for “ON” or 0 for “OFF”. 
4.4.7.  Map Descriptor Example 4 - set aux. aux_num = Boolean 
// Client Side Map Descriptors 
Map Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function, 
Node_Name,  SysPlus_Data_Type,  Address,  Length 
Aux_States_00,  Aux_States_0,  0,  awt,  SYSPLUS_01,  Aux,  0,  1 
The  aux_num  is  specified  by  the  “Address”  field.    The  Boolean  state  of  the  aux  is  retrieved  from  the  value  written  into 
Data_Array_Name at Data_Array_Offset. Use a value of 1 for “ON” and a value of 0 for “OFF”. 