User Guide
FS
-
8700
-
88 Envirotronics SystemsPlus
Page 
10
 of 
49
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: (408) 262-2299 Fax: (408) 262-9042  Toll_Free: 888-509-1970 email: support@fieldServer.com 
4.4.  Client Side Map Descriptors 
4.4.1.  FieldServer Related Map Descriptor Parameters 
Column Title  Function  Legal Values 
Map_Descriptor_Name
Name of this Map 
Descriptor 
Up to 32 alphanumeric 
characters 
Data_Array_Name 
Name of Data Array where 
data is to be stored in the 
FieldServer 
One of the Data Array names 
from “Data Array” section 
above 
Data_Array_Offset 
Starting location in Data 
Array 
0 to maximum specified in 
“Data Array” section above 
Function 
Function of Client Map 
Descriptor 
RDBC, WRBC, WRBX, AWT, 
ART
2
4.4.2.  Driver Related Map Descriptor Parameters 
Column Title  Function  Legal Values 
Node_Name 
Name of Node to fetch data 
from 
One of the node names 
specified in “Client Node 
Descriptor” above 
SysPlus_Data_Type 
Specifies a SystemsPlus data 
type this mapdesc will use 
Refer to Appendix A.1 
SysPlus_Alarm_Name  A SystemsPlus alarm name 
Any four character alarm 
name 
SysPlus_Cmd 
Specifies a SystemsPlus 
command this mapdesc will 
use 
Refer to Appendix A.2 
Store_Data_Array_Name
Name of the data array where 
data must be stored 
Any data array name 
Store_Data_Array_Offset
Offset where data must be 
stored 
0 to maximum offset into 
store data array 
Par_Data_Array_Name 
Name of the data array that 
will contain parameters 
needed by this mapdesc 
Any data array name 
Par_Data_Array_Offset 
Offset where parameters will 
be located 
0 to maximum offset into 
parameter data array 
Address  Starting address 
0 to value allowed for the 
specific mapdesc 
Length  Length of Map Descriptor 
1 to value allowed for the 
specific mapdesc 
4.4.3.  Timing Parameters 
Column Title  Function  Legal Values 
Scan_Interval  Rate at which data is polled  40.001s 
2
 The new ART function stands for “Active Read on Trigger” and is used to effect a single data 
read per trigger. Please refer to the Map Descriptor examples for using this function. 