4.4.4.  Map Descriptor Example 1 – Read 
This example illustrates how to read data from the DataPort. 
 Some basics first: The Map Descriptor is connected to a node by means of the node name and a node definition provides a connection to a port. 
Thus this Map Descriptor is connected to a port via its node. The FieldServer will use that port to send this poll. The poll will be generated every 5 
seconds in this example. 
The values  extracted from the response  will be  stored in the array called  DA_DISPLAY.   Ensure that it is suitable  format for storing  number – 
FLOAT is suggested.  The driver stores the value of the 1
st
 element at offset 1, the 2
nd
 element at offset 2 ….and the driver stores the number of 
table elements whose values have been successfully stored at offset zero. 
// Client Side Map Descriptors 
Map Descriptors 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  Length,  Scan_Interval 
Read_Table_Md ,  Da_Display ,  0 ,  Rdbc ,  FAN01 ,  100 ,  5.0s 
Responses  get 
stored in this  Data 
Array.  Table 
element    x  gets 
stored  at  offset  x, 
where x  is a  non-
zero integer. 
Offset zero is used 
by  the  driver  to 
report  how  many 
value were stored. 
The  driver 
generates  a  read 
poll continuously. 
The  Node_Name 
connects the  Map 
Descriptor  to  a 
Node definition. 
The  length  is  set 
to  a  number  big 
enough  to  contain 
all  the  table’s 
variables. 