4.3.  Client Side Node Descriptors 
Section 
Title 
Nodes 
Column 
Title 
Function  Legal Values 
Node_Name  Provide name for node 
Up  to  32 
alphanumeric 
characters 
Node_ID 
These  correspond  to  the  ‘devices’  configured  in  the 
DTPConfig. Thus the Node_ID is not the address of the final 
CCN device. 
The  DataPort  DTPConfig  table  maps  a  device  number 
(1...15) to a bus number (0-239). Use the Node_ID to tell the 
driver which device to use.  
1-15 
Protocol  Specify protocol used  CarrierDP 
Port  Specify which port the device is connected to the FieldServer  P1-P8, R1-R2
3
Example 
// Client Side Nodes 
Nodes 
Node_Name,  Node_ID,  Protocol ,  Port 
FAN1 ,  1 ,  CarrierDP,  P8 
3
  Not  all  ports  shown  are  necessarily  supported  by  the  hardware.  Consult  the  appropriate  Instruction 
manual for details of the ports available on specific hardware. 