User Guide
FS-8700-86 Carrier DataPort              Page 23 of 32 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970  email: support@fieldserver.com 
Appendix B.4.  How to build a script file that tests a customer log. 
The  following  brief  notes  are  intended  for  configuration  engineers  who  are  expected  to  be  familiar 
with the FieldServer. 
•  Take  the  hex  log  file and  convert  to  ASCII  using  special chars  (this  is  an  option  of  the  log  file 
converter) 
•  Choose a response line from near the end of the log (most recent). Check the line is complete. 
•  Place the line inside an INI file. Make the following changes 
•  Replace [NP] with [FF] 
•  Replace [SP] with a space 
•  Replace [NULL] with a space. 
•  Use the following files as a guide. 
Client.csv 
Data_Arrays 
Data_Array_Name, 
Data_Format, 
Data_Array_Length
DA_D1_01,   Float,  500 
Connections                 
Port ,  Parity, 
Baud, 
Data_Bits, 
Stop_Bits, 
Handshaking, 
Protocol,  Timeout,  Print_storage_locations 
P1,  None,  9600, 
8,  1,  None,  CarrierDP, 
60s,  Yes 
Nodes 
Node_Name, 
Node, 
Protocol, 
Port
Node_A ,  1,  CarrierDP,  P1 
Map_Descriptors             
Map_Descriptor_Name, 
Data_Array_Name, 
Data_Array_Offset, 
Function, 
Node_Name, 
Length, 
Scan_Interval, 
CMD_GP_01,  DA_D1_01,  0,  Rdbc,  Node_A,  202,  5.0s 
Server.csv 
Data_Arrays 
Data_Array_Name, 
Data_Format, 
Data_Array_Length
TABLE_DISPLAY,  Float,  500 
Connections
Port ,  Parity, 
Baud, 
Data_Bits, 
Stop_Bits, 
Handshaking, 
Protocol, 
P1,  None,  1200,  8,  1,  None,  CarrierDP, 
Nodes 
Node_Name, 
Node, 
Protocol, 
Node_A ,  1, 
CarrierDP, 