User Guide
FS-8700-86 Carrier DataPort              Page 13 of 32 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970  email: support@fieldserver.com 
Column Title  Function  Legal Values 
DA_Byte_Name* 
If this parameter is defined then its value must be 
the  name  of  a  Data  Array.    Instead  of  the  driver 
returning  a  static  Field  Status,  it  will  extract  the 
value  located at  the  given offset  and  use  this 
value as the Field Status. 
The  name of  Data  Array 
defined  in  the  Data 
Arrays section. 
On_String 
If  the  variable  has  a  discrete  state,  use  this 
parameter  to  define  the  word  that  describes  the 
state when the variable’s value is 1. 
OR 
Use one of the keywords to tell the driver to send 
the value of the associated array elements: 
NUMERIC – a number 
TIME - a time value formatted as hh:mm 
STRING - a string of bytes 
DOW – occupancy string 
When using the string keyword the driver reads x 
consecutive array  elements  and  treats  them as 
ASCII  character  values  in  forming  the  response. 
X is defined by the length parameter. 
NUMERIC 
TIME 
STRING 
DOW 
Or  any  other  Ascii string 
which  may  not  contain 
spaces. 
Off_String 
If  the  variable  has  a  discrete  state,  use  this 
parameter  to  define  the  word  that  describes  the 
state  when the  variable’s  value is  zero. If you 
have  used  a  keywords  described  above  then 
simply put a dash in this field. 
An  ASCII  string  which 
may not contain spaces. 
Length 
Always set the length to 1 unless you use the key 
word ‘STRING’ as the On_String parameter. 
1 
5.4.3.  Timing Parameters 
Column Title  Function 
Legal 
Values 
Scada_Hold_Timeout
Specifies time Server side waits before responding to Client 
that node is offline on FieldServer Client side. 
>1.0s 










