User Guide
FS-8700-86 Carrier DataPort              Page 12 of 32 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970  email: support@fieldserver.com 
5.4.  Server Side Map Descriptors 
5.4.1.  FieldServer Specific Map Descriptor Parameters 
Column Title  Function  Legal Values 
Map_Descriptor_Name
Name of this Map Descriptor  Up to 32 alphanumeric characters 
Data_Array_Name 
Name of Data Array where data is 
to be stored in the FieldServer 
One of the Data Array names from 
“Data Array” section above 
Data_Array_Location  Starting location in Data Array 
0  to  maximum  specified  in  “Data 
Array” section above 
Function  Function of Client Map Descriptor  passive 
5.4.2.  Driver Specific Map Descriptor Parameters 
Column Title  Function  Legal Values 
Node_Name  Name of Node to fetch data from 
One of the Node Names 
specified in “Server 
Node Descriptor” above 
Length
6
Length  of  Map  Descriptor.    When  reading  a 
compete table, set to the  maximum number of 
data values to be stored. 
1 – 1000 
Table_Name* 
The  name  of  the  table  to  be  polled,  e.g. 
DISPLAY.  This parameter is for display purposes 
only.  The  driver  does  not  use  the  value  of  this 
parameter. 
Some  system  elements  have  multiple  instances 
of  the  same  table  name.  For  example,  the 
Terminal  System  Manager  has  64  Temperature 
Zone configuration tables. The individual tables 
are  named  TZONE1  though  TZONE64.  These 
tables  are  accessed by using  both  the  primary & 
secondary table names. 
E.g. ‘TZCONF TZONE1’ 
Only Ascii characters are 
permitted. 
When using the table 
name parameter to 
specify a primary and 
secondary table, leave a 
single space between 
the two names. 
Field_Name  This is the field variable pneumonic. 
An  Ascii  string  which 
may not
 contain spaces. 
Max length 8 characters. 
Field_Description
Returned when a Client does a read. 
An  Ascii  string  which 
may  contain  spaces.
Max  length  24 
characters. 
Field_Units 
Returned when a Client does a read. If units 
have no meaning for the variable set to zero. 
A  whole  number.  See 
Appendix A.1 
Field Status* 
This  parameter  is  used  to  set  data  quality 
information that is returned when  the Client polls 
for  data.    If  omitted and  DA_Byte_Name has  not 
been  specified  the  driver  returns  zero  as  the 
status value. 
A  whole  number.  See 
Appendix  A.1  for  more 
information. 
6
 Additional information on the length parameter is provided in Appendix A. 