Error Message  Troubleshooting Tip 
Sim4100:#54.  Err.  SeqNumber  check 
disabled. 
Sequence  number  checking  was  disabled.    Check 
your password.  Contact FieldServer Technologies 
for support. 
Sim4100:#55.  Error.  Bad 
Sim4100_Func=%d in MD=<%s> 
Check the CSV file for the correct Simplex function 
type. 
Sim4100:#56  Not used. 
Sim4100:#57*  Err.  Cant  parse  Login 
message. Ignored. 
The  driver  ignored Login  messages.  No  corrective 
action is required. This message is printed for your 
information only. 
Sim4100:#58 FYI. You could have used 
an  Array  called  <%s>  to  expose 
diagnostic info. 
This message is printed for your information only. It 
can safely  be ignored.  For additional information 
read section “Appendix A.7.2 Driver Exposed Stats” 
Sim4100:#59  Err.  Checkpoint.  Report 
this to Tech Support. 
An internal driver diagnostic has been triggered. 
You  must  report  this  error  to  FieldServer’s 
Technical Support. 
Sim4100:#60  Err.  MapDesc=%s.  No 
Node. 
Every Sim4100 Map Descriptor must be connected 
to a node. Ensure that the parameter ‘Node_Name’ 
has been specified on the Map Descriptor. 
To  correct  this  problem,  edit  the  CSV,  make  the 
correction, download the corrected CSV file and 
reset the FieldServer. 
Sim4100:#61  Err.  PLC_Type=4100u 
rqd for 'values'/'earths' 
If you have a Map Descritor which has the 
sim4100_func parameter set to ‘earths’ or to 
‘values’ then you must set the PLC_Type 
parameter on the node to 4100U. (See section 0 
Client  Side  Node  Descriptors  ).  It  is  only 
appropriate to do so if the firmware version of your 
panel  is  10.x  or  later.  You  can  create  a  map 
descriptor to read the version information if you are 
not sure. You can also use the menu system on the 
Panel to read the version number. 
To  correct  this  problem,  edit  the  CSV,  make  the 
correction, download the corrected CSV file and 
reset the FieldServer. 
Sim4100:#62 Err. Input Buffer Overflow.
This  message  is  printed  when  the  input  buffer 
overflows.  This  usually  occurs  when  the  panel 
sends lots of messages and they are not being 
processed  by  the  driver  fast  enough.    A  panic  is 
printed immediate after this message. 
The  driver  will  clear  the  buffer  and  start  capturing 
new  bytes  as  they  arrive.  Messages  may  have 
been lost. We advise that you re-synch the panel. 
This  error has  only  been  seen once. It occurred 
when a panel was connected to the driver with the 
wrong connection settings. 