Technologies Computer Driver Instruction Manual
FS-8700-41 Simplex 4100 Driver Manual            Page 46 of 58 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970  email: support@fieldserver.com 
Error Message  Troubleshooting Tip 
Sim4100:#19e  FYI.  Panel  Firmware 
may be incompatible. 
The  format  of  the  firmware  version  information 
could  not  be  interpreted  correctly.  This  may  mean 
that  your  panel  has  a  firmware  version  that  is  not 
one that the driver explicitly supports. This does not 
mean the driver will not work but if a feature of the 
driver  isn’t  working  correctly  knowing  that  the 
firmware  version  is  not  supported  may  help 
diagnose the problem more easily. 
No corrective action  is  required on  your part.  If 
however,  some  you  suspect  that  the  driver  is  not 
operating correctly it is important that  you mention 
seeing  this  message  in  the  Error  Buffer  when 
reporting the problem. 
Sim4100:#20  FYI.  Data  abandoned! 
Array too short. MapDesc= <%s> 
Check the CSV file Data Array lengths. 
Sim4100:#21. Error.  Data abandoned! 
Array too short c-p-s= %d-%d-%d 
Check the CSV file Data Array lengths. 
Sim4100:#22. FYI. Polling Inhibited. 
Polling  is  disabled  until  the  port  supervision 
message has been received. This message can be 
safely  ignored.  When  the  panel  sends  unsolicited 
messages  to  the  FieldServer  this  message  is 
printed.  Polling  remains  inhibited  until  the 
unsolicited message stream end. 
Sim4100:#23. FYI. Polling Enabled 
When a stream of unsolicited messages is received 
from the Simplex panel then polling is inhibited until 
the  stream  ends.  When  the  stream  ends  this 
message is printed. It may be safely ignored. 
Sim4100:#25. Error.  Data abandoned! 
Array too short c-p-s= %d-%d-%d 
Check the CSV file Data Array lengths. 
Sim4100:#26  FYI.  Data  abandoned! 
Array too short.(%d) MapDesc=<%s> 
Check the CSV file Data Array lengths. 
Sim4100:#27. FYI.  Sequence Number 
reset requested & done. 
Sim4100:#28.  Error.  Bad 
Sim4100_Func=%d in MD=<%s> 
Check  the  CSV  file  and  driver  manual  for  valid 
Simplex functions. 
Sim4100:#29. FYI. Length changed to 1 
in MapDesc= <%s> 
Check  the  CSV  file for  the  correct  Map  Descriptor 
function type. 
Sim4100:#30. FYI. Length changed to 1 
in MapDesc= <%s> 
Check  the  CSV  file for  the  correct  Map  Descriptor 
function type. 
Sim4100:#31. FYI. Length changed to 1 
in MapDesc= <%s> 
Check  the  CSV  file for  the  correct  Map  Descriptor 
function type. 
Sim4100:#32.  FYI.  Sequence  number 
semi-reset. 