Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970  email: support@fieldserver.com 
Array Position  Attribute  Value  Filled In
5
Note
0  Not Defined  10  1  ! 
1  PRIMARY STATUS  14 (Normal)  1  # 
2  PHYSICAL STATE      ~ 
3  RAW STATE       
4  ACTIVE STATE       
5  ARMED STATE       
6  ENABLED STATE  11 (Enabled)  1   
7  UNVERIFIED   0  1   
8  CURRENT DEVICE  4 (Correct Device)  1   
9  DEVICE  12 (On_Line)  1   
10  TEST STATE   3 (Self test normal)  1   
11  PRESENT SENSITIVITY SELECTED       
14  AVERAGE        
17  VALUE  0  1   
18    -41  1   
19        * 
20  PEAK  0  1   
21    -41  1   
22        * 
23  TROUBLE THRESHOLD   6 (Range Normal)  1   
24  OUTPUT STATE        
25  OUTPUT STATUS        
26  DETECTOR SOUNDER        
27  ALARM TEMPERATURE SELECTED=  135  1   
30  DETECTOR RELAY        
Notes: 
! The value 10 represents the count of the number of attributes that were extracted from 
the  response.  It  is  not  equal  to  the  number  of  array  locations  filled  in  because  some 
attributes (e.g. Value) result in more than one array location being updated. 
~ The un-filled-in locations are not updated by the driver when this response is analysed 
because  the  attributes  corresponding  to  these  locations  were  not  reported  in  the 
response to the query. 
* Room for up two three numbers for attributes like value, peak but in this case only two 
values are relevant for this device. 
5
 Locations marked with a 1 are updated when the driver analyses this response 