Appendix A.19. Advanced Map Descriptor Example 10 - Show 
One Map Descriptor is required for each point whose attributes you wish to ‘show’. The show function reads data that describes the 
attributes and the state of each attribute for a single device. Every type of device has a different set of attributes. When the response 
is received by the driver, it fills a number of Data Array locations with numeric values that represent the attributes and their states. 
You should reserve at least 100 array locations for each Map Descriptor by setting the length to 100. 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  Length,  Scan_Interval  sim4100_Func  Sim4100_Card,  Sim4100_Point,  Sim4100_Sub 
Show_mapdesc1,  DA_SHOW,  0,  rdbc,  Node_A,  100,  1.0s,  Show,  1,  2,  3 
By way of example assume that point 1-2-3 is a Heat Detector and the response to the show query is as follows 
40 Character Custom Label 
Mx-y-2   HEAT DETECTOR 
DEVICE ADDRESS: 7-10-2 TYPE: COMBO 
IDNET INTERFACE CARD 
LOCAL UNIT – MAIN PANEL 
UNIT NUMBER: 0 RUI NUMBER: LOCAL 
---------------------------------------- 
PRIMARY STATUS   NORMAL 
CURRENT DEVICE  CORRECT DEVICE 
DEVICE    ON_LINE 
TEST STATE  SELF TEST NORMAL 
ALARM TEMPERATURE SELECTED= 135 DEG F 
VALUE=0 / -41 DEG F 
PEAK=0 / -41 DEG F 
TROUBLE THRESHOLD  RANGE NORMAL 
ENABLED STATE   ENABLED 
UNVERIFIED         0    
The driver will load the array DA_SHOW starting at offset zero for up to 100 elements. Using the following tables we determine what 
values you can expect for this response. 