Appendix A.12. Advanced Map Descriptor Example 3 - Write Panel Time 
Use Ctime to set the panel time and date and use Time just to set the hour minute and seconds. If the hour is zero then the driver 
does not send a write message to the panel. 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  sim4100_func,  Scan_Interval,  Length 
Time_Mapdesc,  DA_TIME,  0,  wrbc,  Node_A,  CTime,,  30s,  7 
Time_Mapdesc,  DA_TIME,  0,  wrbc,  Node_A,  Time,,  30s,  7 
Appendix A.13. Advanced Map Descriptor Example 4 - Panel Revision Information 
It is best to define tie DA_REV_INFO array as format BYTE and if you use RUINET to monitor this Data Array change the display 
format to string so that you can read the information 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  sim4100_func,  Scan_Interval,  Length 
Error_Mapdesc,  DA_REV_INFO,  0,  rdbc,  Node_A,  Revision,  30s,  200 
Index 0: Hour (24 hour clock) 
Index 1: Minute 
Index 2: Second 
Index 3: Day of week 
Index 4: Day of month 
Index 5: Month 
Index 6: Year (since 2000) 
Rdb may be sufficient as this 
data does not change.