Technologies Computer Driver Instruction Manual
FS-8700-41 Simplex 4100 Driver Manual            Page 25 of 58 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970  email: support@fieldserver.com 
Appendix A.3.  How to use Data Arrays to map to/from Card-Point-Sub 
addresses 
Some commands derive a card-point-sub address by inspecting a FieldServer Data Array.  
Others receive data from a device with a card-point-sub address and modify the data in an 
array  based  on  the  card-point-sub  address.    This  section  explains  how  to  make  the 
connection between an index into a Data Array and a card-point-sub address. 
In a simple world the Data Array index would be 
Index = card * max point per card * max sub point per point + point * max sub point per point 
+ sub 
Where max point per card and max sub point per point could be large numbers. 
As you can imagine this would require huge sparse Data Arrays.  To reduce the Data Array 
size the FieldServer uses a mapping algorithm which can be optimized based on the 
addresses  of  the  Simplex  devices.  The  map  is  manipulated  by  using  the 
sim4100_card/point/sub parameter values. 
Example: 
Consider the following Map Descriptor fragment. 
… ,  sim4100_func,
sim4100_card,
sim4100_point,
sim4100_sub,
data_array_offset
  Xpoint, 
10, 
5,  10,  0 
If data is received for point <c>-<p>-<s> = 9-0-0 
This data will NOT be processed because the card number does not match the value of the 
sim4100-card 
If data is received for point <c>-<p>-<s> = 10-20-0, however, the data will be processed. 
The array location is derived using the following formula (sim4100_sub is to be read as the 
“number of sub-points per point”; sim4100_card’s value will be ignored.) 
  Location  = data_array_offset + <p> * sim4100_sub + <s> 
      = 0 + 20 * 10 + 0 = 200 
Appendix A.4.  Simplex Point Status Data Format 
When a point status is obtained the FieldServer will write one byte of data to a Data Array. 
The byte will contain the following information.  Because each point can report a number it 
only makes sense to use Data Arrays that are not bit arrays. 
Bit  Identifier  Description 
0 (First Bit)  F  Fire Alarm 
1  P  Priority 2 
2  S  Supervisory 
3  T  Trouble 
4  U  Utility 
5  C  Control 
6  D  Disable 
7  A  Primary state (based on point type - F if smoke detector, C if signal 
circuit, etc.) 