Technologies Computer Driver Instruction Manual
FS-8700-41 Simplex 4100 Driver Manual            Page 24 of 58 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970  email: support@fieldserver.com 
Appendix A.2.1.  Sim4100_Card Keyword 
The FieldServer will accept any positive integer number including zero; however, not all 
values are valid for Simplex devices. Refer to Note (1). 
Many  commands  and  output  message  contain  system  point  ID  fields.    These  fields 
reflect the way a 4100 point (local, external, real, pseudo), is referred to. 
There  are  two  basic  formats  allowed,  address  format  <apoint>,  and  symbolic  format 
<spoint>. 
In the Simplex device the terminal ADDRESS flag is set (DEFAULT) so that <apoint> is 
always  used  in  computer  messages;  otherwise,  the  symbolic  form  is  used.    The 
FieldServer cannot work with symbolic (spoint) addresses. 
Appendix A.2.2.  <apoint> 
Format <card>-<point>-<sub> 
Legend:   
<card>  4100 card, pseudos included, See note (1) 
<point>  4100 point (sometimes slot), See note (2) 
<sub>  4100 sub-point (sometime point), See note (2) 
Examples:   
0-6-6  Master trouble point (LCD trouble) 
5-0-1  Typical card status point, card at address 5 
3-1-0  Point 1 for card at address 3 
Notes: 
(1)  The following ranges are valid for Simplex Devices: 
Card address
Card type 
0-119  Physical (Hardware) cards
128-143  Digital Pseudo cards 
144-159  Analog Pseudo cards 
160-175  List Pseudo cards 
(2)  The  range  of  point and sub-point fields for point addressing is very sparse and 
depends on the type of card at that location. Contact Simplex Time Company for details 
on point address ranges for specific cards. 
Appendix A.2.3.  Sim4100_Point Keyword 
The FieldServer will accept any positive integer number including zero; however, not all 
the  values  are  valid  for  Simplex  devices  -  see  Sections  6.3  and  6.4  for  further 
information. 
Appendix A.2.4.  Sim4100_sub Keyword 
The FieldServer will accept any positive integer number including zero; however, not all 
the  values  are  valid  for  Simplex  devices  -  see  Sections  6.3  and  6.4  for  further 
information. 