Technologies Computer Driver Instruction Manual
FS-8700-41 Simplex 4100 Driver Manual            Page 17 of 58 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com 
4.5.5.  Map Descriptor Example 1. - Read Point Status 
This Map Descriptor can be used to poll for the status of a particular point.  When the response is obtained the driver sets the value 
of one Data Array element to a number indicating the point’s status. The values are described in Appendix A.4.  You need one such 
Map Descriptor for every point whose status you wish to poll. Notes in Appendix A.13 provide more information 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name  Length  Scan_Interval,  sim4100_func  sim4100_card,  sim4100_point,  sim4100_sub 
A1,  DA_AI3,  0,  RDBC,  Node_A,  1,  5,  Clist,  1,  2,  3 
The Data 
extracted from 
the device is 
placed in this 
driver 
independent 
data array. 
This identifier 
must be the same 
as the node name 
used to identify 
the port connected 
to the Simplex 
device being 
described in this 
map Descriptor. 
Ignored for the 
Simplex protocol 
unless the 
sim4100_func=ackal
l, clearall, 
Simplex Device: Card 
Perform the 'Computer 
List Status' Function to 
(in this case) read the 
current point status of 
the point specified by 
card-point-sub. This 
function returns fire, 
supervisory, trouble.... 
data. The format of the 
returned data is 
described in Appendix A 
The data is 
written into the 
array starting at 
this position. A 
value of zero is 
equivalent to the 
first position. 
Simplex Device: Point
Simplex Device: Sub
-
Point