4.5.4.  Protocol (Simplex Device) Specific Parameters 
Column Title  Function  Legal Values 
sim4100_func 
A keyword which controls the function being 
performed or the type of data being polled / 
written. 
Further notes on 
these keywords 
are provided in 
Appendix A 
Ackall, Setd, 
Disable, Restart, 
Clistall, Clist, 
Time, Ctime, 
Ack, 
Xpoint, Seta, 
Super, Show, 
Earths, Value, 
ClearAll 
The Simplex Time Recorder Company - 4100 Computer Port Protocol only uses the 
standard 4100 address format of <Card>-<Point>-<Sub-point>. Symbolic addressing is 
not supported. The following keywords are used to address devices. 
sim4100_Card  Simplex Address <Card> 
sim4100_Point  Simplex Address <Point> 
sim4100_Sub  Simplex Address <Sub_Type> 
Further notes 
and examples 
are provided in 
Appendix A 
sim4100_WriteThru*
Only appropriate when the 
sim4100_func=clist. 
Controls the write through behavior of the 
clist function. See Appendix A.20 for 
additional information. 
When using the default value then the write 
commands are done using the format SET 
c-p-s ON/OFF. If the parameter is set to 
value then writes are done using the format 
SET c-p-s value. 
Onoff, value 
Store_Unsolicited* 
Control the ability of ‘CLIST’ map descriptors 
to be used to store data from unsolicited 
messages. Refer also to Appendix A.20 
Yes/No 