Technologies Computer Driver Instruction Manual
FS-8700-41 Simplex 4100 Driver Manual            Page 14 of 58 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970  email: support@fieldserver.com 
Example 
// Client Side Nodes 
Nodes       
Node_Name,  PLC_Type,  Protocol,  Connection 
Device1,  4100U,  Sim4100,  P8 
4.4.  Client Side Driver Tables 
A driver table is used to extend a table of values/attributes that have been hard coded into 
the driver. It is possible to extend the tables using CSV file parameters. 
Additional information on the use of these tables may be found in Appendix A.8 
4.4.1.  SHOW Response Attributes Driver Table 
Column Title  Function  Legal Values 
Protocol 
The protocol must be specified on each row 
of a driver table. 
Sim4100 
sim4100_Attr_Name 
The SHOW command response consists of 
a number of attributes and their current 
state/ values. 
Use this parameter to add a new attribute to 
the table. 
The exact 
character 
sequence that 
must be 
specified. May 
include an equal 
sign. 
sim4100_Attr_Offset 
If the response contains the attribute defined 
above, its current state/value must be stored 
at offset x in the associated Data Array. 
Use this parameter to define x. Take care to 
leave enough space for those attributes 
which have multiple values. 
May not be zero. 
sim4100_Attr_Method
This parameter tells the driver how to 
convert the current state/value for storage in 
the Data Array. For example, the driver 
cannot store the state ‘Normal’ . By 
specifying method 1, you tell the driver to 
use the state descriptor ‘Normal’ in a lookup 
table of attribute states to find the value 
associated to Normal and to store that 
value. 
1,2,3 
May not be zero. 