Technologies Computer Driver Instruction Manual
FS-8700-39 EST3 Driver Manual              Page 9 of 21 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com 
4.4.3.  Map Descriptor Example 1 
// Client Side Map Descriptors 
Map_Descriptors                   
Map_Descriptor_Name  ,Data_Array_Name  ,Data_Array_Offset  ,Function  ,Node_Name  ,EST_Panel  ,EST_Card  ,Address  ,Length  ,Scan_Interval 
MD_LED_1  ,DA_AI_01  ,0  ,Rdbc  ,EST_1  ,1  ,1  ,0  ,20  ,5.0s 
4.4.4.  Map Descriptor Example 2: 
This  Map  Descriptor  will  cause  the  specified  EST  point  to  be  read  every  50  seconds  (subject  to  throughput  constraints);  the  full  16-bit  status 
values received from regular polls will be stored in Data Array DA_AI_01 at offsets 0 – 19, and the Alarm, Trouble, Supervisory, Monitor or Other 
status  (received  by  regular poll,  or  Delta message)  will  be  stored  in Data  Arrays  TROUBLES and  ALARMS,  SUPERVISORY,  MONITOR, 
OTHERS also at offsets 0 – 19. Refer also to Appendix C. 
// Client Side Map Descriptors 
Map_Descriptors                       
Map_Descriptor_Name  ,Data_Array_Name  ,Data_Array_Offset  ,Function  ,EST_Trouble_DA  ,EST_Alarm_DA  ,Node_Name  ,EST_Panel  ,EST_Card  ,Address  ,Length  ,Scan_Interval 
MD_LED_1  ,DA_AI_01  ,0  ,Rdbc  ,TROUBLES  ,ALARMS  ,EST_1  ,1  ,1  ,0  ,20  ,50s 