Technologies Computer Driver Instruction Manual
FS-8700-39 EST3 Driver Manual              Page 7 of 21 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970  email: support@fieldserver.com 
4.4.  Client Side Map Descriptors 
4.4.1.  FieldServer Related Map Descriptor Parameters 
Column Title  Function  Legal Values 
Map_Descriptor_Name
Name of this Map Descriptor 
Up to 32 alphanumeric 
characters 
Data_Array_Name 
Name of Data Array where data 
is to be stored in the FieldServer 
One of the Data Array names 
from “Data Array” section above 
Data_Array_Offset  Starting location in Data Array 
0 to maximum specified in “Data 
Array” section above 
Function  Function of Client Map Descriptor
RDBC, WRBC
3
, WRBX 
4.4.2.  Driver Related Map Descriptor Parameters 
Column Title  Function  Legal Values 
Node_Name  Name of Node to fetch data from 
One of the node names 
specified in “Client Node 
Descriptor” above 
EST_Panel  Panel  0 - 63 
EST_Card  Card  0 - 255 
Address  Starting address of read block  0 - 1023 
Length  Length of Map Descriptor 
For Reads: 1 to 34 For Writes: 
1 
EST_Object_Type  Object type parameter 
Relay, Led, ServGroup, 
GuardPtrl, ChkInGrp, 
AltMessage, Reset, PanelSil, 
AlarmSil, Drill, GAInhibit, 
Reboot, Evacuate, AltSensitiv, 
Partition, CmdList, Input, Zone, 
Card, AndGroup, Matrix, 
TimeCtrl, InstructionText, 
AmpPower, AudMsg, CmdList, 
MCmsg, SetDate, SetTime 
EST_Index  Index parameter  0 - 65535 
EST_Route  Route parameter  0 - 255 
EST_Priority  Pri parameter  0 - 4 (see note below) 
EST_Chan  Chan parameter  0 - 255 
EST_Msg_Index  MsgIndex parameter  0 - 65535 
EST_Account  Account parameter  0 - 255 
EST_ConfCL  ConfCL parameter  0 - 65535 
EST_Panel_Mask_1  PanelMask(1) parameter (LSB)  0 - 255 
EST_Panel_Mask_2  PanelMask(2) parameter  0 - 255 
EST_Panel_Mask_3  PanelMask(3) parameter  0 - 255 
EST_Panel_Mask_4  PanelMask(4) parameter  0 - 255 
EST_Panel_Mask_5  PanelMask(5) parameter  0 - 255 
EST_Panel_Mask_6  PanelMask(6) parameter  0 - 255 
EST_Panel_Mask_7  PanelMask(7) parameter  0 - 255 
EST_Panel_Mask_8  PanelMask(8) parameter (MSB)  0 - 255 
Data_Array_Low_Scale*  Scaling zero in Data Array 
-32767 to 32767, 0 
Data_Array_High_Scale*
Scaling max in Data Array 
-32767 to 32767, 100 
Node_Low_Scale*  Scaling zero in Connected Node 
-32767 to 32767, 0 
Node_High_Scale*  Scaling max in Connected Node 
-32767 to 32767, 100 
3
 WRBC is not recommended, as startup values may be invalid 