Type  Encode 
Value 
Alarm
Trouble
Supervisory
Monitor
Others
AccessReaderFault  148 
Y 
AccessInternalFault  149 
Y 
AccessCommunicationFault  150 
Y 
CmdList  151 
Y 
Appendix C.2.  Output data format 
Each  output  device  is  associated  with  a  16-bit  value.  This  value  consists  of  two  byte  fields,  the 
device type (LSB) and the device state (MSB). 
FieldServer Data Array Object (16-bit) 
Attribute (8-bit)  Command (8-bit) 
These  values  are  provided  by  the  EST  panel  and  are  described  in  the  EST3  ECP  protocol 
specification as follows. These values will be put in the Command field. 
Command  Encode Value 
Activate / Away  01h 
Enable  02h 
Restore / Disarm  11h 
Disable  12h 
The attribute byte must be set for writes to Relay and LED outputs. For Relays, the attribute values 
are: 
Attribute (Relay)  Encode Value 
Enable  2h 
Activate  101h 
Restore  11h 
Disable  12h 
For LED’s, the attribute values are: 
Attribute (LED)  Encode Value 
On  101h 
Slow Flash  201h 
Fast Flash  301h 
Disable  12h 
Enable  2h 
Off  1h 