Appendix C.  EST3 Data Format: 
Appendix C.1.  Input data format 
Each input device is associated with a 16-bit value. The contents of the 16 bits are used to generate 
status types  as shown in the table  below.   Each incoming  event is allocated to  a status  type 
depending on its device type as shown in the table.  It is possible to override this default status type 
allocation. Refer to Appendix A.5 for more information. 
Type  Encode 
Value 
Alarm
Trouble
Supervisory
Monitor
Others
Smoke  0  Y 
Pull  1  Y 
Heat  2  Y 
Waterflow  3  Y 
Stageone  4  Y 
Zone  5  Y 
AlarmVerify  6 
Y 
PreAlarm  7 
Y 
Security  8 
Y 
Station  9 
Y 
Emergency  10 
Y 
Supervisory  11 
Y 
Valve  12 
Y 
GateValve  13 
Y 
Tamper  14 
Y 
Temperature  15 
Y 
Power  16 
Y 
Signal  17 
Y 
TroubleOpen  18 
Y 
TroubleShort  19 
Y 
LocalTrouble  20 
Y 
MaintAlert  21 
Y 
DirtyHead  22 
Y 
DeviceComm  23 
Y 
GroundFault  24 
Y 
InternalTrouble  25 
Y 
BadType  26 
Y 
BadPersonality  27 
Y 
UnexpectedDevice  28 
Y 
CommonTrouble  29 
Y 
RelayConfirmation  30 
Y 
Monitor  31 
Y 
LocalMonitor  32 
Y 
Damper  33 
Y 
Fan  34 
Y 
Door  35 
Y 
Switch  36 
Y 
FirePhone  37 
Y 