User Guide
FS-8700-31 Siemens TIWAY I  Page 5 of 23 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
Example
// Client Side Connections 
Connections 
Port,  Protocol,  Baud,  Parity,  Handshaking,  Poll_Delay 
P1,  TIWAY_BDLC,  9600,  None,  None,  0.100s 
4.3.  Client Side Node Descriptors 
Section Title 
Nodes 
Column Title  Function  Legal Values 
Node_Name  Provide name for node 
Up to 32 alphanumeric 
characters 
Node_ID 
Secondary PLC station address to 
communicate with 
1-254 
Protocol  Specify protocol used  TIWAY, TIWAY_BDLC 
Connection 
Specify which port the device is 
connected to the FieldServer 
P1-P8 
Example
// Client Side Nodes 
Nodes       
Node_Name,  Node_ID,  Protocol,  Port 
PLC_01,  01,  TIWAY_BDLC,  P1 
4.4.  Client Side Map Descriptors 
4.4.1. FieldServer Related Map Descriptor Parameters 
Section Title 
Map Descriptors 
Column Title  Function  Legal Values 
Map_Descriptor_Name 
Name of this Map 
Descriptor 
Up to 32 alphanumeric 
characters 
Data_Array_Name 
Name of Data Array 
where data is to be stored 
in the FieldServer 
One of the Data Array names 
from “Data Array” section 
above 
Data_Array_Offset 
Starting location in Data 
Array 
0 to maximum specified in 
“Data Array” section above 
Function 
Function of Client Map 
Descriptor 
RDBC, WRBC, WRBX, AWT 