5.3.3.  Serving TIWAY data map descriptor example 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length 
S01_RAW16_PLC0, RAW16_Data,  0,  Server, PLC_01,  IE_Ladder,  0,  10 
The above map descriptor serves 10 data elements starting from address 0 of type “IE_Ladder” for PLC_01. 
5.3.4. Serving Drum_Count_Preset TIWAY data map descriptor example 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length, 
S10_RAW16_PLC01, RAW16_Data,  71,  Server, PLC_01,  Drum_Count_Preset, 0,  4, 
Preset_Step_List 
3 5 9 167 
The above map descriptor serves 4 data elements starting from address 0 of type “Drum_Count_Preset” for 
PLC_01. Each address location is contiguously associated with a preset step value from the Preset_Step_List field. 
5.3.5.  Serving PLC status data map descriptor example 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Length 
S36_PRIM_STATUS, Status,  0,  Server, PLC_01,  Status_Primitive,  3 
The above map descriptor serves 3 status data elements for PLC_01 in the data array “Status” starting from offset 
0. 